Alarm Levels and Notifiable Events
Mirox watches solar, wind and battery plants with one alarm system. This page lists every event that can notify you, the level it opens at, what triggers it, how fast it is detected and what ends it — so you can decide from which level upwards you want to be told. The tables on this page are generated from the same catalog the platform uses to send notifications, so they always describe what actually happens.
How a finding becomes a notification
- Mirox detects a condition at a plant — a unit stopped by a fault, a data source that went silent, a safety alarm — and opens an event.
- Mirox assigns the level. Every event type has a fixed level from Critical down to Very low. The level is defined by the platform, not by you, and it is the same on every plant — with one exception, operator-defined alarm signals.
- You choose the minimum level per category. On your notification settings, each category (Production, Availability, Alarm system, …) has a minimum level. An event notifies you if its level is at or above that minimum and you have switched on at least one channel for the category.
Why the levels are the same for everyone, and what to do when one does not suit you, is explained under Why levels are fixed.
One notification per situation. A plant with forty inverters, twelve turbines or a dozen battery units does not send forty notifications when a feeder trips. Each unit's own state is recorded as an event at Normal, and the site as a whole raises one notification at High — "components down" — that lists every affected unit and is updated as units join or recover. Only safety alarms bypass this bundling.
The six levels
| Level | Numeric priority | What it means |
|---|---|---|
| Critical | ≥ 1500 | People or the plant may be in physical danger now: fire, smoke, thermal runaway, a fire suppression that released, an arc in a wind turbine or a battery storage system, an intrusion alarm. Sent at once, every time — even during a service visit and even when many arrive together. |
| Very high | ≥ 1300 | A deliberate change disturbs data collection or a capability of the site is lost (a paused or deleted data source, a revoked credential). The default floor of the alarm-system row. |
| High | ≥ 1100 | Units produce nothing because they report a fault, or we have been blind to them or to the whole plant for long — one notification per site situation, not one per unit. |
| Normal | ≥ 900 | A single unit's state behind that site notification, or a device fault while the unit keeps running. Visible in the event list, not notified by default. |
| Low | ≥ 700 | Warnings and housekeeping states (a stop someone ordered), and units we cannot read because their data logger is offline — listed under that logger's notice. |
| Very low | ≥ 0 | Records without operational effect (comments, labels). Never notified. |
| Category | Admin | Moderator | Technical asset manager | Commercial asset manager | Member | External |
|---|---|---|---|---|---|---|
| Production | off (opt-in from Critical) | off (opt-in from Very high) | on from High | off (opt-in from High) | on from Very high | off (opt-in from Very high) |
| Control signals | off (opt-in from Critical) | off (opt-in from Very high) | on from High | off (opt-in from High) | off (opt-in from Very high) | off (opt-in from Very high) |
| Availability | off (opt-in from Critical) | on from Very high | on from High | off (opt-in from High) | on from Very high | off (opt-in from Very high) |
| Sensors | off (opt-in from Critical) | off (opt-in from Very high) | on from High | off (opt-in from High) | off (opt-in from Very high) | off (opt-in from Very high) |
| Alarm system | off (opt-in from Very high) | off (opt-in from Very high) | on from Very high | off (opt-in from Very high) | off (opt-in from Very high) | off (opt-in from Very high) |
| Components | off (opt-in from High) | off (opt-in from High) | off (opt-in from High) | off (opt-in from High) | off (opt-in from Very high) | off (opt-in from Very high) |
| Monitoring agent | on from Critical | on from Critical | on from Critical | on from Critical | on from Critical | on from Critical |
| Tickets | on from Very high | on from High | on from High | on from High | on from Very high | on from Very high |
Critical
People or the plant may be in physical danger now: fire, smoke, thermal runaway, an extinguishing system that released, an electric arc in a wind turbine or a battery storage system, an intrusion alarm. Critical notifications are sent at once, every time — without bundling, also during a service visit, and even when many arrive together.
Typical: a battery container reports thermal runaway; a turbine reports smoke in the nacelle; the site's intrusion alarm is raised. An inverter's own safety alarm (an arc fault or a residual-current fault it reports) is recorded as an event at Normal and is not notified by default.
Very high
A deliberate change disturbs data collection, or a capability of the site is lost — for example a paused or deleted data source, or a revoked credential. No plant-equipment event opens at this level today; it mainly serves as a threshold: it is the default minimum of the Alarm system row (so only the intrusion alarm itself notifies) and of the Member and External roles.
High
Units produce nothing because they report a fault, or we have been blind to them — or to the whole plant — for a long time. One notification per site situation, not one per unit.
Typical: "components down" on a site where two turbines stopped by a fault; a data logger that has delivered nothing for 30 minutes; the monitoring VPN to the site is down; an irradiance sensor confirmed defective; the alarm panel reports a fault.
Normal
A single unit's state behind the site notification, or a device fault while the unit keeps running. Visible in the event list and on the plant pages; most of these do not notify by default.
Typical: one inverter in outage; one turbine stopped by a fault; one battery unit not communicating; a battery converter reporting a fault while it keeps running; the communication cabinet running on its UPS.
Low
Warnings and housekeeping states.
Typical: a string under investigation before it is confirmed; a sensor that reads dark for an hour; a manufacturer warning. A unit that cannot be read because its data logger is offline (… unreachable (logger offline)) is Low too: the logger's data-source notice is the one that notifies.
Very low
Records without operational effect, such as comments or labels. Never notified.
Defaults for your role
You do not have to configure anything: your organization role sets sensible defaults, and you only change what you want to be different.
| Role | Site categories (Production, Availability, Sensors, Control signals) | Alarm system | Monitoring agent |
|---|---|---|---|
| Asset Manager (Technical) | On, from High | On, from Very high | On, from Critical |
| Moderator | Availability on, from Very high; the others off (start at Very high when you switch them on) | Off (Very high) | On, from Critical |
| Admin | Off (start at Critical when you switch them on) | Off (Very high) | On, from Critical |
| Asset Manager (Commercial) | Off (start at High) | Off (Very high) | On, from Critical |
| Member | Production and Availability on, from Very high | Off (Very high) | On, from Critical |
| External | Off (start at Very high) | Off (Very high) | On, from Critical |
- Channels. Site categories notify through the App (notification center, badge and mobile push) by default. Email is off for them by default and can be switched on per category; webhooks are always your own choice.
- Monitoring agent is armed for every role but starts at Critical. Agent actions are Normal or Low, so nothing arrives until you lower the row.
- Why technical managers get High by default: they answer for the plant's operation. High is exactly the level of "the site needs someone": units down, a site you cannot see. Below High you would get every single unit's state, which the site notification already summarises.
Why levels are fixed
A level is a promise about consequences: Critical always means possible physical danger, High always means a site situation that costs production or leaves you blind. That promise only holds if it is the same everywhere, so the levels are defined by the platform — not per customer and not per plant.
- Automation needs one vocabulary. A technical manager who looks after many plants automates the response: a webhook that triggers a call-out, an escalation step that alerts the technician on call. Those steps can only be written once for every situation if every event is tagged the same way on every plant. If levels differed per customer or per plant, a colleague's "High" would mean nothing to you, and the same rule would fire on different things for different people.
- The thresholds are already chosen per data source. The agent at each plant knows how its data arrive and picks reasonable timing for each source: a wind turbine's 10-minute rows from the manufacturer's database are judged differently from a battery's minute-by-minute data (see Timing). What matters is that a real problem is detected and acted on — not a threshold tuned plant by plant.
- If a level does not suit you, tell us. In your notification settings, Suggest a different level on a category or an event sends your suggestion to our support, optionally with the latest example from your plants. We review it and, if it holds, adjust the level for everyone.
What is yours to choose is how far down the list you want to be told: the minimum level per category.
Operator-assigned levels
There is one exception. For signals read by the generic Modbus reader, the level is assigned by the plant's technical operator, per signal — only they know what a contact means on that plant. Every other alarm keeps its fixed, platform-defined level. Whether a signal notifies you still depends only on whether you enabled the Alarm system category and on your own minimum level there (enabled by default only for the technical manager, from Very high).
- Threshold conditions exist only there. A signal of the reader may compare the one device value it reads against a limit (greater or less than, with an optional hysteresis). No other alarm on this page has a threshold you can set.
- Nothing is delayed, unless the operator asks for it. A change becomes an alarm on the next poll (default 60 s, plus about 10 s); nothing is delayed or confirmed twice. The one exception is the optional minimum duration of a signal: its condition has to hold that long before the alarm is raised. Clearing is never delayed.
- Short pulses can be missed. The reader sees a signal only when it polls. A pulse shorter than the polling interval can be missed entirely; choose a shorter interval, or have the controller latch the signal.
- The reader's own fault keeps a fixed level. If the device does not answer three polls in a row, or keeps refusing a configured address, the plant shows 'Alarm signals not readable' — the signals are then unknown, not normal. That event is always High.
See the Generic Modbus reader guide for how levels are chosen.
Metric-based alerts: the Alert Manager
Event alarms keep their fixed levels. For anything you want to watch yourself about a measurement — "tell me when this value crosses that threshold" — your organization defines alert rules in the Alert Manager: thresholds on any platform series or organization metric, with durations, schedules and counting. Each rule sets the level of its own alerts, because only you know what your threshold means. You choose from which level on these alerts notify you in the group Alert Manager of your notification settings.
The conditions on signals of the generic Modbus reader stay where they are: they judge a single device value the reader reads.
Timing: when we know, when we are blind
How fast an event opens depends on what we know:
- When the data says a unit is in fault or stopped, we are not guessing — only a short confirmation stands between the reading and the event.
- When no data arrives, silence is not proof of a fault: a network blip, a logger restart or a software rollout look exactly the same for minutes. So we wait longer before claiming an outage — long enough to clear the gaps a healthy data path shows, short enough that a real loss is still reported the same morning.
Every threshold below is a named constant in the platform's code; the generated tables on this page read the same values.
The data says fault or stop
| Equipment | Unit event | Site notification ("components down") | Why |
|---|---|---|---|
| Wind turbine stopped by a fault or a protection | On the first 10-minute row that reports it | After 2 consecutive fault rows — about 20 minutes (about 23 with data-path lag) | One 10-minute row is already ten minutes of evidence. A single interval can be a stop the turbine resets by itself, so the site notification waits for the second. |
| Battery unit whose status word says fault | After 5 consecutive one-minute samples | After 15 minutes of fault | Battery controllers retry a trip within minutes; a real fault stays (one converter fault we observed stood for 17 hours). |
| Battery unit ordered to charge or discharge that does not move that way | After 15 minutes (at least 12 one-minute readings, one held direction) | 15 minutes later — 30 minutes after it began | Only the direction is judged: a unit delivering less than ordered, or a nearly full (85 % and above) or nearly empty (15 % and below) battery, is not a fault; a single converter sitting out while the others follow is the controller's choice. |
| Inverter / combiner box producing nothing in good light | After 3 judged 5-minute windows — about 20 minutes | 30 minutes later — about 50 minutes after the first zero | Solar outages are inferred (zero output compared with the light), not read from the device, so they need more confirmation. |
| Inverter that reports a fault itself (status or alarm list) | At once, day or night (a Normal event); at night it closes as soon as the inverter reports any other state | 5 minutes later, naming every inverter that did the same and is still down — 30 minutes when the fault was reported before sunrise | The machine's own word needs no inference and no light. At night a fault that clears by itself within minutes is not news (some converters trip briefly on grid disturbances), so the site notice waits for it; one that stands is announced. |
| Park controller whose word says the plant is in fault | After 2 consecutive one-minute reads | — (the controller's fault notifies on its own, Critical) | One controller is the whole tracker field or the whole storage; there is no summary to fold it into. |
| Solar tracker whose error word is set | After 2 field refreshes — about 10 minutes | — (trackers never join "components down") | The field refreshes every row about every 5 minutes; one row of hundreds is a service item, not a plant situation. |
| Safety alarm (wind turbine, battery storage) | At once, no debounce | — (safety alarms notify on their own) | Danger is never debounced. The latency is the data path's own: a turbine's 10-minute data (typically about 10 minutes), the battery check every minute (within about 2 minutes). |
No data arrives
| What is silent | Unit event | Site notification | Why these numbers |
|---|---|---|---|
| One turbine, while the other turbines of the site deliver | After 30 minutes (three missed rows) | After 3 hours; after 12 hours if the turbine's last state was a service visit or a commanded stop | A healthy turbine's newest row is 1–11 minutes old, rarely 19. Service visits that switch a turbine's communication off with it last 0.5–4.5 hours. |
| The whole turbine data source (the SCADA database) | — | Source availability when its newest row is older than 30 minutes, measured against the database's own clock | Over 38 park-months there was not a single whole-site gap longer than 30 minutes; both real outages observed (56 and 73 minutes) are caught. Measuring against the database clock keeps a software rollout on our side from triggering it. |
| One battery unit, while its data source keeps delivering | After 15 minutes | After 30 minutes | Measured over 30 days on six storage sites: units report every 60–68 seconds; gaps of a single unit while the others delivered stayed at or below 2.5 minutes (99.9th percentile), the largest jitter seen was 5.7 minutes, and there was no false gap of 5 minutes or more. The real losses (27, 162 and 178 minutes) are all caught. The rule is "the larger of 15 minutes and three times the 99.9th-percentile gap" — here 15 minutes. |
| One solar tracker, while the field keeps refreshing | After 3 refreshes without a record — about 15 minutes | — (trackers never join "components down") | While the rest of the field still refreshes, the silence is the row's own, not the data path's. |
| A park controller | After 15 minutes without a reading | — | The controller is read every minute, so 15 minutes is fifteen missed reads. |
| One inverter / combiner box, while its siblings report | After 1 hour of daylight | No-communication summary: one notice per batch, held 20 minutes after the first silent unit; later units go in a new batch | Inverters sleep at night and wake at different times; the clock only runs in daylight. A dead logger silences a whole station at once and its units open over about 15 minutes, so the hold gathers them into one notice. Sent even when the logger itself is already reported offline: that notice says data is missing, this one names the units. |
| A data source (logger, SCADA database, battery controller) | — | Source availability after 30 minutes (or three of its own reporting intervals, if it reports less often); checked every 5 minutes, so 30–35 minutes | Long enough to ride out a restart or a short network interruption. |
| The VPN to the site | — | About 8–11 minutes: three failed one-minute checks after the handshake went stale, plus a 5-minute hold | The hold drops the short nightly 1–3 minute blips, so they notify nobody. |
| The site network (gateway, devices) while the VPN is up | — | Three failed one-minute checks plus the 5-minute hold | As above. |
VPN alarms apply only to sites with a configured VPN (a direct VPN or a VPN peer); a configured VPN that is down raises VPN offline.
Silence clocks stop when a bigger cause is known
A unit's silence clock only runs while the rest of its data source still delivers. When the whole source or the link to the site is down, one event speaks for all of it — Source availability or VPN offline — instead of one per unit. Solar inverters and combiner boxes are the exception: while the rest of the site reports, the No-communication summary names them after an hour of daylight even when their own logger is down, because it says which units are blind.
Data cadence (10-minute turbine rows)
Turbine data reaches Mirox through the turbine manufacturer's SCADA database as 10-minute rows: the row for 10:00–10:10 exists shortly after 10:10. With the database's own delay (about one minute) and our poll, the newest row is normally 1–11 minutes old. This is why nothing about a turbine can be known faster than about ten minutes — and why the wind thresholds are counted in rows. Battery units report every minute and solar components are judged in 5-minute windows, so their thresholds are counted in minutes.
Resolution notices
When the condition behind a notification ends — the unit produces again, the data source delivers again, the panel is reset — Mirox closes the event and sends a resolution notice on the same channels, so you know you can stand down. The original notification is marked resolved in your notification center.
- An event that closes again during its hold (for example a 2-minute VPN blip) sends neither a notification nor a resolution notice.
- One-off notices — a ticket comment, an action on the monitoring agent, an inverter replacement to confirm — have nothing to resolve and send none.
The Resolution notice column of the category tables below shows which events send one.
Categories
Each row on your notification settings is one category. The tables list every event that can notify in that category.
Production
Units that stop producing, safety alarms of wind turbines and battery storage, and implausible production. This is the category for every plant type: a solar inverter, a turbine and a battery unit that stop are reported the same way — as members of the one site notification.
| Event | Level | Triggers when | Timing | Applies to | Resolution notice |
|---|---|---|---|---|---|
Battery safety alarmcomponent_battery_safety_alarm | Critical | A battery container or converter reports a danger: a fire alarm, smoke or gas detection, thermal runaway, or a released fire suppression. Checked every minute and sent at once. | Device signal: at once | Battery storage | yes |
Park controller faultcomponent_plant_controller_fault_stop | Critical | The central controller of a tracker field or a battery plant reports the plant in fault for two consecutive one-minute reads: the whole field is parked or the whole storage tripped. One controller, so the notice is sent alone — there is no summary to fold it into. | Data says fault: 2 min | Solar trackers, Battery storage | yes |
Park controller safety alarmcomponent_plant_controller_safety_alarm | Critical | The central controller of a tracker field or a battery plant reports a danger: a fire alarm, smoke or gas detection, or a released fire suppression on the plant level. Checked every minute and sent at once. | Device signal: at once | Solar trackers, Battery storage | yes |
Tracker safety alarmcomponent_tracker_safety_alarm | Critical | A solar tracker row reports a danger class. No such class is known for the first fielded system; the alarm exists so a future controller that reports one is handled like every other unit. | Device signal: at once | Solar trackers | yes |
Turbine safety alarmcomponent_turbine_safety_alarm | Critical | A wind turbine reports a danger: fire or smoke, or an arc in the converter or switchgear. Sent with the first data row that carries it (the SCADA data arrive every 10 minutes), also during a service visit. | Device signal: at once | Wind turbines | yes |
Overproductionoverproduction | High | The plant reports more than 125 % of what a clear sky allows, or more than 100 % for 30 minutes — almost always a frozen or mis-scaled meter, not real production. | Data says fault: at once | Solar (inverters, combiner boxes, strings) | yes |
Component outage summarysummary_component_outage | High | Units of the site are down: producing nothing, stopped by their own fault, or — a battery storage — not moving in the direction it is ordered to (charge or discharge). ONE notification per site situation, however many units join or leave. Solar: about 50 minutes after the first zero; a silent inverter counts only once it is shown to be down; an inverter that reports a fault itself (status or alarm list) opens its own outage at once; the site notice follows 5 minutes later (30 minutes when the fault was reported before sunrise, so a trip that clears by itself is not announced), naming every inverter that did the same in that time and is still down, also while the site notice already stands. Wind turbines: two fault rows (about 20 minutes). Battery storage: 15 minutes of fault, or 15 minutes without moving in the ordered direction, and then 15 more. | Data says fault — Solar (inverters, combiner boxes, strings): data says fault 50 min; Wind turbines: data says fault 20 min; Battery storage: data says fault 15 min | Solar (inverters, combiner boxes, strings), Wind turbines, Battery storage | yes |
Combiner box production outagecomponent_gak_outage | Normal | A combiner box produces nothing for three consecutive 5-minute checks although there is enough light — about 20 minutes. Joins the site notice after 30 more minutes. A combiner box that sends no data can also be escalated here by hand: an operator moves it from "not communicating" with a comment, and the notice names who did it and why. | Data says fault: 20 min | Solar (inverters, combiner boxes, strings) | yes |
Inverter production outagecomponent_inverter_outage | Normal | An inverter produces nothing for three consecutive 5-minute checks although there is enough light — about 20 minutes. An inverter that sends no data at all lands here too when the plant's own feed-in meter shows, in two separate hours, that it cannot have produced. One unit's state: by default you are told through the site notice ("components down") it joins after 30 more minutes. An inverter that sends no data can also be escalated here by hand: an operator moves it from "not communicating" with a comment, and the notice names who did it and why. | Data says fault: 20 min | Solar (inverters, combiner boxes, strings) | yes |
String Outagecomponent_string_outage | Normal | A string's outage is confirmed: zero under an overcast sky with enough irradiance on the modules (about 20 minutes), or zero through the next day's high sun. | Investigated: 20 min | Solar (inverters, combiner boxes, strings) | yes |
String Investigationcomponent_string_investigation | Low | A string reads zero for about 20 minutes. The first, unconfirmed stage: shading, snow and soiling look the same at first, so this stays low until it is confirmed. | Investigated: 20 min | Solar (inverters, combiner boxes, strings) | yes |
Availability
Data sources, the VPN, the site network and network devices that stop reporting. A dead or refusing data logger notifies once, through its data source; the units behind it are recorded as unreachable (logger offline) at Low and never notify on their own, and a logger whose components measure wrongly is one Logger measurement issue (Normal, not notified).
| Event | Level | Triggers when | Timing | Applies to | Resolution notice |
|---|---|---|---|---|---|
Network Device Mass Outageavailability_network_devices_mass_outage | High | More than 30 % of a site's network devices have each been unreachable for at least 15 minutes. | No data: 18 min | Network and VPN | yes |
Park Network Offlineavailability_park_network_offline | High | The site's own network (its gateway and devices) failed three consecutive one-minute checks while the VPN itself is up. Held 5 minutes like the VPN notice. | No data: 3 min + 5 min hold | Network and VPN | yes |
VPN Offlineavailability_vpn_offline | High | The monitoring VPN tunnel to the site has had no handshake for three consecutive one-minute checks. A further 5-minute hold drops short blips, so a real outage is reported about 8 to 11 minutes after it starts. | No data: 6 min + 5 min hold | Network and VPN | yes |
Source Availabilitysource_availability | High | A data source of the site (a data logger, a SCADA mirror, a battery controller) has delivered no data for 30 minutes — or for three of its own reporting intervals, if it reports less often. This is the one notification for a data logger that is offline or refuses the login; the units behind it are counted in the event, their production unknown. | No data: 30 min | Solar (inverters, combiner boxes, strings), Wind turbines, Battery storage, Solar trackers, Irradiance sensors, Alarm system | yes |
No-communication summarysummary_component_no_communication | High | Units of the site have delivered no data of their own while the rest of the site reports: inverters and combiner boxes after an hour of daylight, wind turbines after 3 hours (12 hours after a service visit or a commanded stop), battery units after 30 minutes. ONE notification per batch: the notice is held 20 minutes after the first silent unit and names every unit that went silent in that time and is still silent; units that go silent later are announced in a new batch. Units whose data logger is itself reported unavailable are not announced here — the data-source notice covers them. | No data — Solar (inverters, combiner boxes, strings): no data 1 h; Wind turbines: no data 3 h; Battery storage: no data 30 min + 20 min hold | Solar (inverters, combiner boxes, strings), Wind turbines, Battery storage | yes |
Network Device Offlineavailability_network_device_offline | Normal | A monitored network device (switch, router, logger) failed three consecutive polls — about 5 minutes. Not sent while the whole site is offline, and not for devices whose data source is already reported. | No data: 5 min 30 s | Network and VPN | yes |
Control signals
Commands from outside the plant: grid-operator and direct-marketer curtailments. Each one is recorded as a Detected curtailment episode and settled (see Events). That event can notify, but at level Low — below every role's default — so it reaches you only if you lower the Control signals row to Low. It sends no all-clear: the episode's end is noted on the event, which stays open until the month's curtailments are settled. A stop the grid operator or the marketer orders is status, never a fault, so it does not count as a unit down either. The settlements calculated afterwards appear under Curtailment analysis.
| Event | Level | Triggers when | Timing | Applies to | Resolution notice |
|---|---|---|---|---|---|
Curtailment detectedpark_curtailment_detection | Low | The grid operator's or the direct marketer's power limit for the site drops below what the plant could feed in. Read from the limit signal every 5 minutes, so the event opens about 8 minutes after the limit starts. Level low: sent only to users who set the Control signals row to Low. | Data says fault: 8 min | Solar (inverters, combiner boxes, strings) | no |
Sensors
Irradiance sensors that stop measuring plausibly — first an unconfirmed investigation, then a confirmed defect.
| Event | Level | Triggers when | Timing | Applies to | Resolution notice |
|---|---|---|---|---|---|
Sensor Defectcomponent_sensor_defect | High | A sensor defect is confirmed: three hours of daylight readings contradicted by its siblings or by the plant's own production. | Investigated: 3 h | Irradiance sensors | yes |
Sensor Investigationcomponent_sensor_investigation | Low | An irradiance sensor reads dark for an hour of daylight while the plant produces. The first, unconfirmed stage. | Investigated: 1 h | Irradiance sensors | yes |
Alarm system
The plant's alarm signals — see Alarm System. They come from two sources: signals the plant's technical operator defined with the generic Modbus reader, whose level is set per signal, and the fixed contacts of existing WAGO installations (the intrusion alarm panel and the supervision contacts of the communication cabinet), whose levels are listed below. The row has its own group on the settings page and starts at Very high, so by default only signals at Very high or Critical notify — among the fixed contacts, the intrusion alarm itself.
| Event | Level | Triggers when | Timing | Applies to | Resolution notice |
|---|---|---|---|---|---|
Alarm raisedalarm_triggered | Critical | The site's intrusion alarm panel raises an alarm. Mirrored as the panel reports it — within about half a minute, without any delay of our own. | Device signal: 25 s | Alarm system | yes |
Main switch offalarm_cabinet_main_switch_off | High | The main switch of the communication cabinet is off. | Device signal: 25 s | Site | yes |
UPS alarmalarm_cabinet_ups_alarm | High | The uninterruptible power supply of the communication cabinet reports a fault — monitoring may be lost at the next mains outage. | Device signal: 25 s | Site | yes |
Alarm panel faultalarm_fault | High | The alarm panel reports a fault of its own — intrusion detection may be impaired. | Device signal: 25 s | Alarm system | yes |
Alarm signals not readablealarm_reader_fault | High | The device a signal reader polls did not answer three polls in a row, or keeps refusing a configured address — about three minutes at the default interval. | No data: 3 min | Site, Alarm system | yes |
Heating breaker trippedalarm_cabinet_heating_breaker_tripped | Normal | The circuit breaker of the cabinet heating has tripped. | Device signal: 25 s | Site | yes |
UPS on batteryalarm_cabinet_ups_on_battery | Normal | Mains power to the communication cabinet is lost and the UPS carries it. | Device signal: 25 s | Site | yes |
Operator-defined signalalarm_signal | set per signal | A signal your organisation defined on a Modbus device (a contact, a status bit or a measured value against a limit) reports its condition. Mirrored as read — one polling interval (60 s by default) plus about 10 s, without any delay of our own. A pulse shorter than the polling interval is not seen. If your organisation gave the signal a minimum duration, the condition has to hold without interruption for that long before the signal reports; it clears at once. | Device signal: 1 min 10 s | Site, Alarm system | yes |
Monitoring agent
Administrative actions on the site's monitoring agent: assignment, pause, restart, upgrade. Armed for every role but floored at Critical, so nothing arrives until you lower the row.
| Event | Level | Triggers when | Timing | Applies to | Resolution notice |
|---|---|---|---|---|---|
Agent assignedagent_assigned | Normal | An administrator assigned a monitoring agent to the site. | One-off | Monitoring agent | no |
Agent operator changedagent_operator_changed | Normal | The site's monitoring agent moved to another operator. | One-off | Monitoring agent | no |
Agent pausedagent_paused | Normal | The site's monitoring agent was paused — no data is collected until it resumes. | One-off | Monitoring agent | no |
Agent moved to another node (rebalance)agent_rebalanced_local | Normal | The site's monitoring agent was rebalanced within its cluster. | One-off | Monitoring agent | no |
Agent moved to another region (rebalance)agent_rebalanced_regional | Normal | The site's monitoring agent was rebalanced to another region. | One-off | Monitoring agent | no |
Agent restartedagent_restarted | Normal | The site's monitoring agent was restarted. | One-off | Monitoring agent | no |
Agent moved to another operatoragent_shifted | Normal | The site's monitoring agent moved to another operator together with the site's VPN service. | One-off | Monitoring agent | no |
Agent unassignedagent_unassigned | Normal | An administrator removed the site's monitoring agent. | One-off | Monitoring agent | no |
Agent upgradedagent_upgraded | Normal | The site's monitoring agent was upgraded to a new version. | One-off | Monitoring agent | no |
Agent deployment spec updatedagent_deploy_spec_updated | Low | The deployment settings of the site's monitoring agent were changed. | One-off | Monitoring agent | no |
Legacy agent config removedagent_legacy_config_deleted | Low | The manual configuration override of the site's monitoring agent was removed. | One-off | Monitoring agent | no |
Legacy agent config setagent_legacy_config_set | Low | A manual configuration override was set on the site's monitoring agent. | One-off | Monitoring agent | no |
Agent resumedagent_resumed | Low | The site's monitoring agent was resumed. | One-off | Monitoring agent | no |
Components
Changes to the site's equipment that need your confirmation — for example an inverter that looks replaced.
| Event | Level | Triggers when | Timing | Applies to | Resolution notice |
|---|---|---|---|---|---|
Inverter replacement detectedcomp_solar_inverter_replacement_detected | High | An inverter has been silent for 48 hours while a new unit reports on the same logger — most likely a swap. One notice asks you to confirm it so the new unit is analysed. | One-off: 2 d | Solar (inverters, combiner boxes, strings) | no |
Vendor alarms
The device's own alarm and warning list — of inverters, wind turbines, battery storage, solar trackers and park controllers alike — copied as the manufacturer sends it and never judged by Mirox. These records are detail behind the judged events in Production and Components, and they appear under this category in the event list whatever the plant type. Records from before this category existed keep their earlier one, Production or Battery. No event notifies in this category, so it has no row on your notification settings.
Curtailment analysis
What the platform calculates after a curtailment has ended: the settlement of each measure with its legal method and figures, the monthly value per plant and later official price corrections, as well as recalculations of these settlements. They are bookkeeping, not alarms — no event notifies in this category, so it has no row on your notification settings. Records from before this category existed keep their earlier one, Control signals or Monitoring agent.
Production analysis
The monthly summary of what inverter faults cost the plant in production, per inverter. Calculated after the fact from the events in Production, it is bookkeeping, not an alarm — no event notifies in this category. Records from before this category existed keep Production.
Tickets
Tickets you create, are assigned to, comment on or are mentioned in. Mentions and assignments always reach you, whatever your settings.
| Event | Level | Triggers when | Timing | Applies to | Resolution notice |
|---|---|---|---|---|---|
Ticket assignedticket_assigned | High | A ticket was assigned to you. | One-off | Site | no |
Mentioned in a ticketticket_mention | High | Someone mentioned you in a ticket. Always delivered, whatever your settings. | One-off | Site | no |
Ticket unassignedticket_unassigned | High | A ticket was taken off you. | One-off | Site | no |
Ticket closedticket_closed | Low | A ticket you take part in was closed. | One-off | Site | no |
Ticket reopenedticket_reopened | Low | A ticket you take part in was reopened. | One-off | Site | no |
Ticket updatedticket_updated | Low | The status, assignee or category of a ticket you take part in changed. | One-off | Site | no |
Ticket comment addedticket_comment_created | Very low | Someone commented on a ticket you take part in. | One-off | Site | no |
Organization
Members joining or leaving, invitations, role changes and cooperations with other organizations. These notices concern your organization, not a plant, so they carry no detection timing; your role decides which of them are on by default.
Wind turbines
Mirox judges each turbine from its own 10-minute data and notifies on the judged state, not on raw manufacturer codes:
- Stopped by a fault (or a protection): the turbine reports a fault stop. The unit event opens on the first such row; the site notification "components down" follows after two consecutive rows.
- Not communicating: the turbine's rows stop while the other turbines of the site still deliver — after 30 minutes for the unit, 3 hours for the site notification (12 hours after a service visit or a commanded stop).
- Safety alarm (Critical): fire or smoke, or an arc in the converter or the switchgear. Sent with the first row that carries it, also during a service visit.
Stops that are not faults. A turbine stands still for many reasons that are perfectly in order. These are recorded as status — they open no event, never notify and only pause the clock that watches for silence:
- a remote pause from the turbine's control system;
- environmental curtailment: bat protection, shadow flicker, ice, noise reduction;
- a stop ordered by the direct marketer or the grid operator;
- a pause pressed on the turbine's keyboard or a service stop by a technician;
- automatic routines such as yaw untwisting.
Manufacturer codes are detail. The turbine's own alarm code and text travel with the event, so you can see why it stopped — but a code alone never notifies. Plain manufacturer warnings stay visible on the turbine's alarm list on the wind plant pages and do not notify. They are filed under Vendor alarms in the event list.
Battery storage
Battery units — the power converters (PCS) and the battery containers — are judged the same way, from the status word they report every minute:
- Stopped by a fault: the status word says fault for 5 consecutive minutes; the site notification follows at 15 minutes.
- Not communicating: one unit's data stops while its data source still delivers — 15 minutes for the unit, 30 minutes for the site notification.
- Device fault while running (Normal, event only): the unit reports a fault of its own but keeps operating — a service item, not a stop.
- Not following dispatch (Normal, joins the site notification): the unit is ordered to charge or discharge — by the plant controller, by its own converter setpoint or by the marketer, whichever the site uses — and for 15 minutes does not move in that direction or moves against it, while the storage as a whole does not follow either. Only the direction counts: delivering less than ordered is following. It is not judged while the unit is stopped by command, by a protection or by a fault, cannot be read, is nearly full under a charge order (85 % and above) or nearly empty under a discharge order (15 % and below), has nothing to charge from or its charging is capped to zero, or while feed-in is forbidden. The site notification follows 15 minutes later. The event closes only when the unit (or the storage as a whole) follows an order again — a withdrawn order or a unit that cannot be judged right now leaves it open, so it does not open and close with every coming and going of the order — and at once when the unit's own fault stop, safety alarm or silence takes over.
- Safety alarm (Critical): a fire alarm, smoke or gas detection, thermal runaway, a released fire suppression or an arc. Checked every minute and sent at once. A fault of the fire-detection equipment itself (a sensor or panel error) is a device fault, not a safety alarm.
Idle, standby and stops that someone ordered are status, never faults.
Storage on solar and wind plants. These checks run wherever battery hardware is present — not only on plants of type Battery. A solar plant with a storage system gets the same battery alarms, and a hybrid site still raises one site notification that lists inverters and battery units together.
Battery events appear in the event list under the same categories as those of the other plant types — faults, stops and safety alarms under Production, a unit that stops communicating under Availability, the manufacturer's own alarm list under Vendor alarms; earlier records may still show the Battery category. They notify through the Production row of your settings — there is no separate battery row to configure. See Battery Storage.
Solar trackers and park controllers
A solar tracker row is judged from the record the field controller refreshes about every five minutes. One row of hundreds is a service item, so its events stay at Normal or below, never notify on their own, and trackers are never members of the site notification "components down":
- Stopped by a fault (Normal): the row's error word stays set for two refreshes, about 10 minutes.
- Not communicating (Normal): no record for three refreshes, about 15 minutes, while the field keeps refreshing.
- Misaligned (Low): at least 10° off its setpoint for three refreshes, about 15 minutes, while it is tracking and no stow, override or cleaning stands on the field controller.
- Safety alarm (Critical): a danger class reported by the row. No tracker danger class is known today; the alarm exists so a future controller that reports one is handled like every other unit.
A stow for wind, snow or low light, an override, a cleaning run or an emergency stop is status, not a fault.
A park controller — the optional central controller of a tracker field or a battery plant — stands for the whole field or storage, so it is judged as a plant situation:
- Fault (Critical): the controller reports the plant in fault for two consecutive one-minute reads. It notifies on its own — there is no summary to fold it into — and sends a resolution notice when it clears.
- Not communicating (Normal): no reading for 15 minutes.
- Safety alarm (Critical): a fire alarm, smoke or gas detection or a released fire suppression on the plant level. Checked every minute and sent at once.
- Stopped by command (Low, never notifies): standby, night mode, a stow for wind, snow or low light, an operator override or a cleaning run. It is the explanation the other checks read — a tracker standing still in a stowed field is not misaligned.
The manufacturer's own alarm and warning list of both is filed under Vendor alarms. Tracker and park-controller events appear under the same categories as those of every other unit and notify through the Production row of your settings. See Solar Trackers and Park Controllers.
Examples by level
Real, anonymised cases per level, newest first.
| Level | Event | Example |
|---|---|---|
| Critical | Battery safety alarmcomponent_battery_safety_alarm | Typical case: a rack's gas detector trips stage 1 in a storage container; the notice goes out within two minutes. |
| Critical | Park controller faultcomponent_plant_controller_fault_stop | A storage plant controller reported fault after a protection trip at 10:21; the notice went out at 10:23 and the resolution at 11:05. |
| Critical | Park controller safety alarmcomponent_plant_controller_safety_alarm | Typical case: a storage plant controller mirrors its fire panel; the notice goes out within two minutes. |
| Critical | Tracker safety alarmcomponent_tracker_safety_alarm | None recorded yet. |
| Critical | Turbine safety alarmcomponent_turbine_safety_alarm | A turbine reported arc light in its converter during a service visit; the safety notice would have gone out with the first data row, about 10 minutes later. |
| Critical | Alarm raisedalarm_triggered | Typical case: a site's intrusion alarm trips at night; the notification goes out about 25 seconds later and clears when the panel is reset. |
| High | Overproductionoverproduction | Typical case: a meter keeps reporting its midday value after its clock stopped; the notice clears when the reading updates. |
| High | Component outage summarysummary_component_outage | An inverter outage at sunrise rolled up into the site notice at 07:46; it closed at 10:46 when the last unit recovered. |
| High | Network Device Mass Outageavailability_network_devices_mass_outage | Sixteen of nineteen devices on a hybrid PV and storage site went dark one evening; the notice stood for 15 hours and cleared the next morning. |
| High | Park Network Offlineavailability_park_network_offline | A site's network was lost at 09:23 and restored at 12:36. Most such interruptions last about 4 minutes and are absorbed by the hold. |
| High | VPN Offlineavailability_vpn_offline | A site's VPN dropped at 22:59 and the notification followed a few minutes later; it reconnected at 10:01 the next morning. Several 2-minute blips that month notified nobody. |
| High | Source Availabilitysource_availability | A logger delivered its last reading at 11:28; the notification went out at 11:58 and the all-clear at 14:08 when data returned. |
| High | No-communication summarysummary_component_no_communication | A station lost its supply in the evening; next morning its 20 inverters had been silent for an hour of daylight, and the notice named them all 20 minutes later. |
| High | Sensor Defectcomponent_sensor_defect | An irradiance sensor confirmed defective at 13:30 kept the event open until 14:40 the next day. |
| High | Main switch offalarm_cabinet_main_switch_off | On the same storage site the cabinet main switch was off for 21 hours after a service visit. |
| High | UPS alarmalarm_cabinet_ups_alarm | A cabinet UPS raised an alarm at 07:40, reported 30 seconds later; it stayed open for days until the battery was replaced. |
| High | Alarm panel faultalarm_fault | Typical case: the panel loses a detector line and reports a fault until a technician repairs it. |
| High | Alarm signals not readablealarm_reader_fault | Typical case: the controller in the transfer station loses its network link; after three minutes the plant shows that its alarm signals are not being read. |
| High | Inverter replacement detectedcomp_solar_inverter_replacement_detected | An inverter silent for more than two days was matched to a newly reporting unit on the same logger; the operator confirmed the swap the same day. |
| High | Ticket assignedticket_assigned | A ticket was opened 19 minutes after a battery over-temperature fault and assigned to the site's technician. |
| High | Mentioned in a ticketticket_mention | A colleague asked you to check a battery fault. |
| High | Ticket unassignedticket_unassigned | A ticket was reassigned to a colleague. |
| Normal | Combiner box production outagecomponent_gak_outage | A combiner box read zero from 12:50; the event opened at 13:10 and closed at 16:10. |
| Normal | Inverter production outagecomponent_inverter_outage | An inverter dropped to zero at 11:20 in good light; the event opened at 11:40 and closed at 14:20. |
| Normal | String Outagecomponent_string_outage | A string confirmed out at 10:15 closed at 14:15 when it produced again. |
| Normal | Network Device Offlineavailability_network_device_offline | A switch stopped answering at 12:35; the event opened about 5 minutes later and closed at 15:26. |
| Normal | Heating breaker trippedalarm_cabinet_heating_breaker_tripped | A storage site's cabinet heating breaker tripped at 19:45 together with the main switch; both were restored at 17:04 the next day. |
| Normal | UPS on batteryalarm_cabinet_ups_on_battery | Typical case: a short grid interruption at the site puts the cabinet on battery for a few minutes. |
| Normal | Agent assignedagent_assigned | A new site got its monitoring agent assigned during onboarding. |
| Normal | Agent operator changedagent_operator_changed | A site's agent was moved to another cluster operator. |
| Normal | Agent pausedagent_paused | An agent was paused during a site's network rebuild. |
| Normal | Agent moved to another node (rebalance)agent_rebalanced_local | An agent was rebalanced to another node at 03:12. |
| Normal | Agent moved to another region (rebalance)agent_rebalanced_regional | An agent moved to the second data centre during maintenance. |
| Normal | Agent restartedagent_restarted | An agent was restarted to apply a configuration change. |
| Normal | Agent moved to another operatoragent_shifted | A site's VPN service was reassigned to another operator, and its agent moved with it. |
| Normal | Agent unassignedagent_unassigned | A decommissioned site's agent was removed. |
| Normal | Agent upgradedagent_upgraded | An agent was upgraded during the weekly roll-out. |
| Low | String Investigationcomponent_string_investigation | A string went dark at 07:10; the investigation opened at 07:30 and closed at 10:05 when it produced again. |
| Low | Curtailment detectedpark_curtailment_detection | Typical case: the grid operator caps a site at 60 % around midday for redispatch; the episode is recorded with its start and end, and the production chart of that day shows the cap. |
| Low | Sensor Investigationcomponent_sensor_investigation | A pyranometer went dark at 06:15; the investigation opened at 07:20 and closed at 09:20 when readings returned. |
| Low | Agent deployment spec updatedagent_deploy_spec_updated | An agent's resources were raised after a site grew. |
| Low | Legacy agent config removedagent_legacy_config_deleted | The legacy override was removed after the migration. |
| Low | Legacy agent config setagent_legacy_config_set | A legacy configuration was applied during a migration. |
| Low | Agent resumedagent_resumed | The agent resumed after the network rebuild. |
| Low | Ticket closedticket_closed | A ticket about an inverter fault was closed after the repair. |
| Low | Ticket reopenedticket_reopened | A ticket was reopened when the fault came back. |
| Low | Ticket updatedticket_updated | A ticket moved to "in progress" when a technician took it. |
| Very low | Ticket comment addedticket_comment_created | A technician posted photos from the site visit. |